• Alarmeinstellungen für GaswarngeräteAllgemeine Schulung zu Gasen

     

    VOR HAUPT MAK KZE
    *O2 19,5% vol 23,5% vol n.v. n.v.
    *CO 35 ppma, b 70 ppmb 35 ppma  200 ppm
    *H2S 10 ppm 20 ppm 10 ppm 15 ppm
    *SO2 2,0 ppm 4,0 ppm 2,0 ppm 5,0 ppm
    *NO2 3,0 ppm 6,0 ppmc 3,0 ppm 5,0 ppm
    *Cl2 0,5 ppm 1,0 ppm 0,5 ppm 1,0 ppm
    *ClO2 0,1 ppm 0,2 ppm 0,1 ppm 0,3 ppm
    CO2 0,5% vol 1,0% vol 0,5% vol 3,0% vol
    PH3 0,3 ppm 0,6 ppm 0,3 ppm 1,0 ppm
    NH3 25 ppm 50 ppm 25 ppm 35 ppm
    HCN 5,0 ppm 10,0 ppm 4,0 ppm 4,0 ppm
    NO 25 ppm 50 ppm 25 ppm 25 ppm
    HCl 2,5 ppm 5,0 ppm 2,5 ppm 2,5 ppm
    H2 50 ppm 100 ppm n.v. n.v.
    CH4 1,0% vol 1,5% vol n.v. n.v.
    LEL 10% LEL 20% LEL n.v. n.v.
    PID 100 ppm 200 ppm n.v. n.v.
     Hinweis:
    a. Da für CO das OSHA-PEL 50 ppm beträgt, verwendet Industrial Scientific den im Jahr 1989 festgelegten Standard (35 ppm). All alarm set points are field adjustable over the full range of the sensor, exceptions: LEL/CH4 – 0 to 60% and 0 to 3,0% by vol CH4. Provided standards exist, all alarm settings are based on the following: Niedrigalarmsignale basieren auf OSHA PEL- und/oder NIOSH-Werten. Hohe Alarme basieren auf den doppelten OSHA PEL-Werten.

    b. MSHA CO limits are 50 ppm for a low alarm and 100 ppm for a high alarm.

    c. MSHA NO2 limits are 5 ppm for a high alarm.